HostingOur sitesOwn a siteAbout usArticlesFAQContact

Hydro miner hosting: what your machines need from a site

← All articles·November 2026·3 min read

Hydro miners are more demanding than air-cooled ones. They need the right power, the right water and the right cooling, and the manufacturer's conditions are precise. Here is what a site has to provide, taken from Bitmain's own specification sheets.

  • 380–415 Vthree-phase powerBitmain
  • 8–10 L/minwater flow per machineBitmain
  • ≤3.5 barwater pressureBitmain
  • 20–50 °Cinlet water range, S21 XP HydBitmain

Two formats, one cooling principle

Hydro miners come in two shapes. Some are tower-sized units, about the size of a desktop computer case: Bitmain's S21 Hyd measures 339 × 163 × 207 mm and weighs 12.3 kg. Others are flat units that slide into a rack, server-style, for higher density. Both run on the same principle: a water loop through cold plates on the hashboards. We host both formats, from Bitmain and other manufacturers.

Power

Bitmain's S21 Hyd and S21 XP Hyd run on three-phase power, 380 to 415 V AC, 50 or 60 Hz, at around 12 A. A household or single-phase supply won't do. At their typical setting, these two models draw about 5.4 and 5.7 kW. You pay for that power at one rate per kWh, and the rate covers almost everything else.

Water

Hydro miners on a rack, with their water and power connections.
Hydro miners on a rack, with their water and power connections.

Bitmain's specifications for the water are precise:

RequirementValue
Flow per machine8 to 10 L/min
Pressure3.5 bar at most
FluidDeionized or pure water, antifreeze allowed on S21 XP Hyd
pH8.5 to 9.5
ConductivityUnder 20 µS/cm at first start, replace at 100 µS/cm
ConnectorDN10

Source: Bitmain, S21 Hyd and S21 XP Hyd specifications.

  • Flow: 8 to 10 litres per minute per machine.
  • Pressure: 3.5 bar at most.
  • Fluid: deionized or pure water, and for the S21 XP Hyd, antifreeze is allowed.
  • Quality: pH between 8.5 and 9.5. Conductivity must be under 20 µS/cm at first start, and the fluid must be replaced once it reaches 100 µS/cm.
  • Connection: DN10 pipe connectors.

Temperature

Inlet water must sit in a set range. For the S21 Hyd, Bitmain gives 35 °C in normal mode, 45 or 50 °C in high-energy modes. The S21 XP Hyd accepts 20 to 50 °C, and won't start below 20 °C.

The dry cooler has to match. With Bitmain's own dry cooler, water at 35 °C allows outside air up to 30 °C; water at 50 °C allows up to 45 °C. In the north, keeping the loop warm enough in winter matters as much as the summer limit.

In the north, keeping the loop warm enough in winter matters as much as the summer limit.

What we check before quoting

When you write to us, we ask for:

  • the model and format of your machines,
  • how many,
  • the power setting you plan to run.

From that we check power capacity, water flow and cooling capacity on our sites, and come back with a written quote. You can already see which sites have open slots.